Operating modes, Start-up disabler (input parameter aust), Standard function blocks – Pilz PSS SB HYD, Basic license User Manual
Page 174: Sb075
6-112
Modular Block System: Hydraulic Presses
Standard Function Blocks
Operating modes
Start-up disabler (input parameter
AuSt)
If the start-up disabler is active (
AuSt = 0), you will need to reset after each
• PSS warm start
• PSS cold start or
• SafetyBUS p: I/O-Group start (input parameter
GRP must be assigned
the status flags of the relevant I/O-Groups)
Only then can the enable be given. If a function test is also required (see
input parameter
NoFT), this must first be completed without error and then
reset. If no other errors are present, the enable will be set.
If the start-up disabler is not active (
AuSt = 1), the enable will be set
directly if no more errors are present. If a function test is required (see
input parameter
NoFT), this must first be completed without error.
shut
-
-
-
-
-
-
open
x
-
-
-
-
-
shut
-
x
x
x
x
-
open
x
x
x
x
x
-
shut
-
-
-
-
-
x
open
x
-
-
-
-
x
shut
-
x
x
x
x
x
open
x
x
x
x
x
x
Yes
No
Yes
No
Yes
No
Start-up disabler (
AuSt
)
Function test required (
NoFT
)
Status of gate on start-up
Close gate
Request (
RQST
)
Open gate
Close gate
Request (
RQST
)
Reset (
RSET
)
Note: This procedure is independent of the status of the input parameter
ARSt
SB075
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license