Settings for the parameters ton and toff, Poppet valves, Directional control valves – Pilz PSS SB HYD, Basic license User Manual

Page 216: Setting reaction times, Standard function blocks, Sb089

background image

6-154

Modular Block System: Hydraulic Presses

Standard Function Blocks

• Please note:

- With directional control valves (input parameter

VTyp = 0), the reaction

time when the valve switches on and off must always be monitored
(see under “Settings for the parameters

TOn and TOff”).

- With poppet valves, the reaction time when the valve switches on and

off may be monitored (see under “Settings for the parameters

TOn and

TOff”).

Settings for the parameters

TOn and TOff

Poppet valves

I/P Parameter

TOff = 0

0<

TOff

max

VTyp = 1

TOn = 0

Reaction time is not

Reaction time is monitored

monitored with the valve

when the valve switches

switches on or off

off

0<

TOn

max

Reaction time is

Reaction time is

monitored when the valve

monitored when the valve

switches on

switches on and off

Directional control valves

I/P Parameter

0<

TOff

max

VTyp = 0

0<

TOn

max

Reaction time is monitored when the valve
switches on and off

Setting reaction times

• Select a low value (e.g. 10 ms)

• Increase the value step by step (max. 10 ms steps), until it is clear that

the valve operates safely and correctly.
This will ensure that reaction times correspond to the actual values of the
valve.

SB089