Modular Block System: Hydraulic Presses

Standard Function Blocks

• Bit 09:

Error can only be reset at the extreme top position (ETP) of the

press.
Remedy: Move press to extreme top position (ETP); check all
conditions, error resets automatically at ETP

• Bit 10:

Press overrun is too long, i.e. the test cam (TLS) was passed

on the overrun measurement; the press is disabled.
Remedy: Move press to extreme top position (ETP); check all
conditions, then reset (input parameter:

RSET), repeat overrun

measurement

• Bit 11:

The signal from the test cam (TLS) is missing when starting

the overrun measurement from the extreme top position (ETP).
Remedy: Check all conditions, then reset (input parameter
RSET)

• Bit 12:

Test cam (TLS) reached and the extreme top position (ETP) is

still free.
Remedy: Move press to extreme top position (ETP); check all
conditions, then reset (input parameter:

RSET)

Global parameters used in the administration blocks

Global parameters are set in OB120 using SB071.

• DW 1022: Minimum PSS scan time

Blocks required

• DB015:

Administration data block

DB015 must consist of its total length of 1024 data words and
have READ/WRITE access (see section entitled
“Administration data blocks” in Chapter 5).