Error messages, Standard function blocks sb069 – Pilz PSS SB HYD, Basic license User Manual
Page 138
6-76
Modular Block System: Hydraulic Presses
Standard Function Blocks
SB069
permitted duration of the whole test on type 2 ESPE/AOPDs is 150 ms
(EN 61 496-1, see also SB071/DW1006).
DANGER!
The automatic function test of the ESPE/AOPD must only be carried out
via the input parameter
Test at a time when the guarding function of the
ESPE/AOPD will not be called upon.
INFORMATION
If an external switch is used to trigger the automatic function test of the
ESPE/AOPD, the feasibility and function of this external switch must be
tested by the user.
Error messages
Any fault that is detected will be stored in the corresponding error data
word (
SSNR) of the administration data block (1st data block), until the
fault has been fully dealt with.
• Error messages in DB015
- Bit 00:
ESPE/AOPD output signal 1 and 2 (input parameter
NO_1 and
NO_2) are not synchronised.
Remedy: Check ESPE/AOPD outputs, cable, input card and
all conditions, and then carry out a function test.
- Bit 02:
Time exceeded on automatic function test of ESPE/AOPD
Remedy: Check ESPE/AOPD outputs, cable, input card and
all conditions, and then carry out a function test.
- Bit 05:
Start-up disabler; not yet reset
Remedy: Reset (input parameter
RSET)
Otherwise: Check switch, cable, input card and all conditions,
and then reset.
- Bit 06:
Reset constantly pressed or pressed too early
Remedy: Reset input parameter
RSET
Otherwise: Check switch, cable, input card and all conditions,
and then reset.
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license