6-76

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB069

permitted duration of the whole test on type 2 ESPE/AOPDs is 150 ms
(EN 61 496-1, see also SB071/DW1006).

DANGER!

The automatic function test of the ESPE/AOPD must only be carried out
via the input parameter

Test at a time when the guarding function of the

ESPE/AOPD will not be called upon.

INFORMATION
If an external switch is used to trigger the automatic function test of the
ESPE/AOPD, the feasibility and function of this external switch must be
tested by the user.

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of the administration data block (1st data block), until the

fault has been fully dealt with.

• Error messages in DB015

- Bit 00:

ESPE/AOPD output signal 1 and 2 (input parameter

NO_1 and

NO_2) are not synchronised.
Remedy: Check ESPE/AOPD outputs, cable, input card and
all conditions, and then carry out a function test.

- Bit 02:

Time exceeded on automatic function test of ESPE/AOPD
Remedy: Check ESPE/AOPD outputs, cable, input card and
all conditions, and then carry out a function test.

- Bit 05:

Start-up disabler; not yet reset
Remedy: Reset (input parameter

RSET)

Otherwise: Check switch, cable, input card and all conditions,
and then reset.

- Bit 06:

Reset constantly pressed or pressed too early
Remedy: Reset input parameter

RSET

Otherwise: Check switch, cable, input card and all conditions,
and then reset.