Pilz PSS SB HYD, Basic license User Manual

Page 171

background image

Modular Block System: Hydraulic Presses

6-109

AuSt:

Automatic start/start-up disabler
AuSt = 0: Start-up disabler (initial reset is required)
AuSt = 1: Automatic start/no start-up disabler on PSS cold/
warm start or when starting the I/O-Group
(see also under “Operating modes”)

WARNING!

A plant or machine may only be operated with an automatic
restart or automatic start if the risk analysis of the plant or
machine has guaranteed this will not cause a hazard. An
automatic restart may not be set, for example, if it is possible
to access the safety gate from behind.

NoFT:

Function test on the gate
NoFT = 0: Function test required on the gate when the PSS is
cold/warm started, when the I/O-Group is started or each time
the gate is unlocked
NoFT = 1: No function test required
(see also under “Operating modes”)

BLNK:

Flash mode for status indicator
(see Output parameters

SGrd and SLck)

RSET:

Reset input
RSET = 0/1 pulse edge:
- Reset errors or
- Reset start-up disabler or
- Reset reset lock