Modular Block System: Hydraulic Presses

Standard Function Blocks

Y:

Output parameters for operating a valve
Y = 0:

Valve off

Y = 1:

Valve on

ERR:

This output parameter is set as soon as a fault is discovered.
ERR = 0:

No fault found

ERR = 1:

Fault found

Function

• Switches on the valve in its start position only (input parameter

S = 1,

valve de-energised, acknowledgement from valve is present).

• Monitors position through acknowledgement of the valve's position (input

parameter

S) within a maximum reaction time. The reaction time for

switch on and switch off may be selected individually:

- Reaction time when switching on the valve:

When switched on, the valve must leave its start position within a
maximum time (reaction time). The maximum reaction time when
switching on the valve can be set via the input parameter

TOn. If the

maximum reaction time is exceeded, an error message will be issued
(output parameter

ENBL = 0 and ERR = 1) and the valve will switch off

immediately (output parameter

Y = 0). A reset will be necessary (see

also under “Error messages”).

- Reaction time when switching off the valve:

When switched off, the valve must reach its start position within a
maximum time (reaction time). The maximum reaction time when
switching off the valve can be set via the input parameter

TOff. If the

maximum reaction time is exceeded, an error message will be issued
(output parameter

ENBL = 0 and ERR = 1) and a reset will be

necessary (see also under “Error messages”).

• Monitors position through acknowledgement of the valve's position (input

parameter

S), without setting a maximum reaction time (input parameter

TOn = 0 and TOff = 0).
When monitoring the position of a valve without monitoring the reaction
time, SB087 checks that it leaves its start position (valve de-energised,
acknowledgement present) at least once in each working cycle (valve
switching on and off). If this is not the case, SB087 will register an error
(output parameter

ENBL = 0 and ERR = 1) and the valve will switch off

immediately (output parameter

Y = 0). A reset will be necessary (see

also under “Error messages”).

SB087