Solare Datensysteme Solar-Log User Manual
Page 55

55
Operating via a web browser within your own network
Type of Reactive Power Reduction:
This contains the type of reactive power reduction that is specified by the active control source.
Displayed Text
Explanation
Text
PMF_RP_NONE
No reactive power control.
PMF_RP_ERROR
An error occurred while determining the reactive power control
function.
PMF_RP_FIX_COS
Fixed Cos(Phi) specification.
PMF_RP_FIX_Q
Fixed reactive power specification.
PMF_RP_Q_U_LINE
Reactive power determined by the characteristic curve Q(V)
PMF_RP_P_PN_LINE
Cos(Phi) determined by the configured characteristic curve P/Pn
PMF_RP_ADJUSTABLE
The control function is determined by an input (e.g. via a ripple
control receiver or IO Box/Profile).
PMF_RP_MATRIX
The Cos(Phi) specifications are determined by the the config-
ured matrix.
Value specification from:
This field indications how the control value used was determined.
Displayed Text
Explanation
Text
PMV_NONE
No control source.
PMV_CONFIG
The value is stored in the configuration.
PMV_MODE
The value can be determined by the reduction mode.
PMV_RP_PIGGY
The value comes from the PM (reactive power control) input
(and is determined in combination with the matrix in the config-
uration or PM profile).
PMV_MRP_PIGGY
The value comes from the PM (reactive power control) input of
the master (and is determined in combination with the matrix in
the configuration or PM profile).
PMV_MODBUS_1
The value comes from the ModBus PM V1 interface.
PMV_MODBUS_2
The value comes from the ModBus PM V2 interface.
PMV_PROFILE_ADAM
The value comes from the analog or digital input of the IO Box
(Adam Box).
PMV_PROFILE_INTERN
The value is specified in the PM profile.
PMV_ERROR
An error occurred while determining the value.
PMV_CONFIG_UTILITY
The value was determined via the internal configuration based
the Utility Meter measurement.
PMV_MODBUS_DM
The value comes from the ModBus DM interface (direct seller
interface).