Operating via a web browser within your own network
There is also a
10% Diagnosis Function
to simulate a dynamic reduction to 10%.
The values are displayed in the table.
Note
!
The 10% Diagnosis Function can only be used when the 70% Fixed Reduction has
been activated.
Explanation of the Values in the Power Reduction Section
The following values are displayed in the Power Reduction section:
Power reduction type determined by:
The currently active control source is indicated in this field.
Displayed Text
Explanation
Text
PMC_NONE
No control source.
PMC_DIAG
Controlled by the diagnostic mode.
PMC_MODBUS_2
Controlled by the ModBus PM V2 (new ModBusPM).
PMC_MODBUS_1
Controlled by the ModBus PM V1 (old ModBusPM).
PMC_PROFILE
Controlled by the PM Profile.
PMC_INTERN
Controlled by the internal configuration.
PMC_DM_MODBUS
Controlled by direct seller via ModBusDM.
PMC_DM_RCR
Controlled by direct seller via ripple control receiver
Type of Reduction:
This contains the current type of power reduction that is specified by the control source.
Displayed Text
Explanation
Text
PMF_NONE
No power reduction function.
PMF_PR_ERROR
An error occurred while determining the power reduction func-
tion.
PMF_PR_FIX_PERC
Fixed reduction at % DC.
PMF_PR_FIX_KW
Fixed reduction at X kW (AC)
PMF_PR_VAR_PERC
Fixed reduction at % DC with self-consumption calculation.
PMF_PR_VAR_KW
Fixed reduction at X kW (AC) with self-consumption calculation.
PMF_PR_FIX_MATRIX
Reduction based on the value from the matrix (ripple control
receiver configuration).
PMF_PR_VAR_MATRIX
Reduction based on the value from the matrix (ripple control
receiver configuration) with self-consumption calculation.