Pac Correction Factor

The correction factor can be adjusted yearly after receiving the statement from the utility company.

Example calculation:

Inverter 1

Inverter 2

Calibrated power meter

Total energy

Total energy

Total energy

259.12 kWh

305.22 kWh

550.55 kWh

Total = 564.34 kWh

Deviation= 13.79 kWh

By comparing the values, you see that the inverters are more likely to display too much output.

Pac Correction Factor

Calibrated power meter total energy

Inverter total energy

550.5 kWh

564.34 kWh

Calculated PAC correction factor in the example:

(550.55 kWh/564.34 kWh)* 1000= 975.66

Rounded PAC correction factor = 976