Trace parameters – KACO blueplanet 750 - 1000 kVA User Manual

Page 92

background image

Page 92

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Parameters

Parameters

Min

Max

Unit

Parameters

IINV Voltage Build
Up Time

0

9999

msec

Since the time of this parameter after “Initial
Voltage Build-up” is started, check synchroniza-
tion of between inverter and grid voltage

IINV PLL Stabiliza-
tion Time

0

9999

msec

Check the voltage phase between inverter and
grid during the time of this parameter

IINV PLL P Gain

0

299.99

-

P gain of grid voltage PLL used at “Initial Voltage
Build-up”

IINV PLL I Gain

0

299.99

-

I gain of grid voltage PLL used at “Initial Voltage
Build-up”

IINV Synchroniza-
tion Tolerance

1

20

degree

Determine the threshold value of the synchroniza-
tion between inverter and grid voltage at “Initial
Voltage Build-up” state

FRT Overcurrent
Protection Time

0

5000

msec

The power generation is stopped for this param-
eter value after fault clear in FRT situation.

Power Control
Enable

0

1

-

Use Power Control structure

APS Lower DB

0.02

3

Hz

Lower limit of frequency Anti-Islanding (APS)

CC PI Cutoff Freq.

0

100

Hz

Cutoff frequency of current controller PI-gain

Table 16: Controller Parameters

Trace Parameters

Parameters

Min

Max

Unit

Descriptions

Trace Mode

0

10

N/A

0: Fault Trace Data
11: Trace Data After Pre-sync. to the grid

Trace Sample Time

0

9999

CCP

Sampling Time of Trace Data

Trace 1

0

999

N/A

Select Trace Data 1 Value

Trace 2

0

999

N/A

Select Trace Data 2 Value

Trace 3

0

999

N/A

Select Trace Data 3 Value

Trace 4

0

999

N/A

Select Trace Data 4 Value

Trace 5

0

999

N/A

Select Trace Data 5 Value

Trace 6

0

999

N/A

Select Trace Data 6 Value

Trace 7

0

999

N/A

Select Trace Data 7 Value

Trace 8

0

999

N/A

Select Trace Data 8 Value

Trace 9

0

999

N/A

Select Trace Data 9 Value

Table 17: Trace Parameters