Page 111

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 111
Parameters
Figure 88: The graph of VDPR in Stop Decrease Mode
If {Voltage Dependant Power Reduction Mode} value is ‘1’, VDPR Mode is linear mode. Above the figure, if
the grid voltage rises to {Voltage Dependant Power Reduction Voltage Level 1}, the output power of inverter
decreases linearly. Although the active output power of inverter is limited, the gird voltage will increase continu-
ously. the Inverter will be stopped by over voltage protection.