KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 121

Parameters

Tab

Number Parameter

Min

Max

Default Value

Grid

2

Grid Over Voltage Level 1

105

130

110%

3

Grid Under Voltage Level 1

75

100

90%

4

Grid Over Frequency Level 1

0

3

0.2Hz

5

Grid Under Frequency Level 1

0

3

2Hz

12

Grid Over Voltage Level 2

105

130

120%

13

Grid Under Voltage Level 2

15

100

80%

14

Grid Under Frequency Level 2

0

3.5

2.5Hz

15

Grid Over Voltage Level 1 Trip Time

100

10000

5000msec

16

Grid Over Voltage Level 2 Trip Time

40

2000

100msec

17

Grid Under Voltage Level 1 Trip Time

100

10000

5000msec

18

Grid Under Voltage Level 2 Trip Time

40

3000

100msec

19

Grid Under Frequency Level 1 Trip
Time

100

20000

10000msec

20

Grid Under Frequency Level 2 Trip
Time

40

3000

100msec

21

Grid Over Frequency Level 1 Trip Time 40

3000

100msec

Table 34: Related Parameters (ex. BP1000 Model)