2 overview of operating states – KACO blueplanet 750 - 1000 kVA User Manual
Page 37

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 37
Storage/Installation/Start-up
5.7.2 Overview of operating states
Figure 24: Overview of operating states
Tag
Parameter
Default Value
T
Shift
Time Shift (Grid tab)
0sec
V
pv_start
MPPT V Start (PV Array tab)
700V
T
start
MPPT T Start (PV Array tab)
900sec
V
mpp_min
MPPT V Minimum (PV Array tab)
505V
P
stop
MPPT P Stop (PV Array tab)
7kW (above 550kVA capacity: 8kW)
T
stop
MPPT T Stop (PV Array tab)
60sec
Table 2: Parameters of operating states