Faults and Warnings
Message
Code
Description
Grid Phase Jump
26
Grid side Voltage phase delay accident
Grid Phase Open
27
Grid side Voltage phase open accident
MC21(Inv. MC of PEBB 2)
Failure
28
Inverter side contactor (MC21 of PEBB 2) failure
MC21(Inv. MC of PEBB 3)
Failure
29
Inverter side contactor (MC21 of PEBB 3) failure
Grid Over Voltage 1
30
Grid side Voltage over the parameter [Grid Over Voltage Level 1]
Grid Under Voltage 1
31
Grid side Voltage under the parameter [Grid Under Voltage Level 1]
Grid Over Frequency 1
32
Grid side Frequency over the parameter [Grid Over Frequency Level 1]
Grid Under Frequency 1
33
Grid side Frequency under the parameter [Grid Under Frequency Level 1]
Grid CB Trip
34
CB20 (AC Disconnect/Grid circuit breaker) was tripped during opera-
tion
Grid Over Voltage 2
35
Grid side Voltage over the parameter [Grid Over Voltage Level 2]
Grid Under Voltage 2
36
Grid side Voltage Under the parameter [Grid Under Voltage Level 2]
Grid Under Frequency 2
37
Grid side Frequency Under the parameter [Grid Under Frequency Level 2]
Grid Over Frequency 2
38
Grid side Frequency Over the parameter [Grid Over Frequency Level 2]
Parameters Version Error
40
Different version between the NVSRAM parameter table and the
program parameter table
Flash Memory Failure
41
C6000 DSP program flash memory failure in XCU (main control) board
FPGA Failure
42
FPGA failure in XCU (main control) board
DSP28x Failure
43
F2000 DSP failure in XCU (main control) board
ADC Failure
44
ADC block failure in XCU (main control) board
NVSRAM Failure
45
NVSRAM Failure in XCU (main control) board or invalid parameter set-
ting
Asynchronous
46
Synchronous fail of Grid and Inverter
CAN Failure
47
CAN bus communication failure
Emergency Stop
50
The door is open/The emergency stop botton is pressed
Master Slave Fault
52
Master Slave operation Failure
PEBB Current Unbalance(R) 53
The unbalanced current between PEBBs (R Phase)
PEBB Current Unbalance(S) 54
The unbalanced current between PEBBs (S Phase)
PEBB Current Unbalance(T) 55
The unbalanced current between PEBBs (T Phase)
Grid Over Frequency Level 3 57
Grid side Frequency over the parameter [Grid Over Frequency Level 3]
Grid Under Frequency Level 3 58
Grid side Frequency under the parameter [Grid Under Frequency Level 3]
Grid Over Voltage Slow
59
Grid side Voltage over the parameter [Grid OverVoltage Level Slow]
(RMS average value per 10min)
HMI-XCU Communication
Error
63
HMI-XCU communication Error
Table 6: Fault