Faults and Warnings

Message

Code

Description

Grid Phase Jump

26

Grid side Voltage phase delay accident

Grid Phase Open

27

Grid side Voltage phase open accident

MC21(Inv. MC of PEBB 2)
Failure

28

Inverter side contactor (MC21 of PEBB 2) failure

MC21(Inv. MC of PEBB 3)
Failure

29

Inverter side contactor (MC21 of PEBB 3) failure

Grid Over Voltage 1

30

Grid side Voltage over the parameter [Grid Over Voltage Level 1]

Grid Under Voltage 1

31

Grid side Voltage under the parameter [Grid Under Voltage Level 1]

Grid Over Frequency 1

32

Grid side Frequency over the parameter [Grid Over Frequency Level 1]

Grid Under Frequency 1

33

Grid side Frequency under the parameter [Grid Under Frequency Level 1]

Grid CB Trip

34

CB20 (AC Disconnect/Grid circuit breaker) was tripped during opera-
tion

Grid Over Voltage 2

35

Grid side Voltage over the parameter [Grid Over Voltage Level 2]

Grid Under Voltage 2

36

Grid side Voltage Under the parameter [Grid Under Voltage Level 2]

Grid Under Frequency 2

37

Grid side Frequency Under the parameter [Grid Under Frequency Level 2]

Grid Over Frequency 2

38

Grid side Frequency Over the parameter [Grid Over Frequency Level 2]

Parameters Version Error

40

Different version between the NVSRAM parameter table and the
program parameter table

Flash Memory Failure

41

C6000 DSP program flash memory failure in XCU (main control) board

FPGA Failure

42

FPGA failure in XCU (main control) board

DSP28x Failure

43

F2000 DSP failure in XCU (main control) board

ADC Failure

44

ADC block failure in XCU (main control) board

NVSRAM Failure

45

NVSRAM Failure in XCU (main control) board or invalid parameter set-
ting

Asynchronous

46

Synchronous fail of Grid and Inverter

CAN Failure

47

CAN bus communication failure

Emergency Stop

50

The door is open/The emergency stop botton is pressed

Master Slave Fault

52

Master Slave operation Failure

PEBB Current Unbalance(R) 53

The unbalanced current between PEBBs (R Phase)

PEBB Current Unbalance(S) 54

The unbalanced current between PEBBs (S Phase)

PEBB Current Unbalance(T) 55

The unbalanced current between PEBBs (T Phase)

Grid Over Frequency Level 3 57

Grid side Frequency over the parameter [Grid Over Frequency Level 3]

Grid Under Frequency Level 3 58

Grid side Frequency under the parameter [Grid Under Frequency Level 3]

Grid Over Voltage Slow

59

Grid side Voltage over the parameter [Grid OverVoltage Level Slow]
(RMS average value per 10min)

HMI-XCU Communication
Error

63

HMI-XCU communication Error

Table 6: Fault