KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 81

Parameters

Parameters

Min

Max

Unit

Descriptions

Grid Over Voltage
Level 2 Trip Time

40

2000

ms

Time for grid over voltage level 2 trip

Grid Under Voltage
Level 1 Trip Time

100

10000

ms

Time for grid under voltage level 1 trip

Grid Under Voltage
Level 2 Trip Time

40

3000

ms

Time for grid under voltage level 2 trip

Grid Under Fre-
quency Level 1 Trip
Time

100

20000

ms

Time for grid under frequency level 1 trip

Grid Under Fre-
quency Level 2 Trip
Time

40

3000

ms

Time for grid under frequency level 2 trip

Grid Over Frequency
Level 1 Trip Time

40

3000

ms

Time for grid over frequency level 1 trip

FRT Enable

0

1

-

FRT (Fault Ride Through) Function
0: Disable
1: Enable

Grid Over Voltage
FRT Enable

0

1

Over Voltage FRT Function
0: Disable
1: Enable

Power Reduction
Gradient Level

0

100

%/Hz

Gradient level for frequency dependant power
reduction

Power Reduction
Deactivation
Frequency

0

0.3

Hz

Frequency limit for frequency dependant power
reduction deactivation

Grid Over Frequency
Level 2

0

3

Hz

Upper limit for grid over frequency level 2

Grid Over Frequency
Level 2 Trip Time

40

2000

ms

Time for grid over frequency Level 2 trip

Reconnection
Condition Mode

0

3

-

Reconnection Condition Function
0: Disable
1: Checked before connected to grid
(Germany Medium Voltage Requirements)
2: Checked according to VDE-AR-N 4105
(Germany Low Voltage Requirements)

Reconnection
Condition Upper
Voltage

-1

130

%

This parameter represents the upper voltage in the
range of “Reconnection condition” as a percent-
age of the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.

Table 12: Grid Parameters