5storage/installation/start-up, 1 storage – KACO blueplanet 750 - 1000 kVA User Manual
Page 20

Page 20
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Storage/Installation/Start-up
5
Storage/Installation/Start-up
5.1 Storage
When inverter is stored the following conditions are required. If not, this may cause failures. The company will
not be responsible for the problems if following condition is not observed.
•
The unit should be stored indoor in its original packaging when it’s being stored more than 6 months. If its
original packaging is removed, it should be stored indoor in a cool, dry place.
•
When the unit is stored outdoor, please keep the remained original packaging and do not leave the unit out-
side more than 3 days.
•
Storage temperature: -20°C ~ +70°C
•
Relative humidity: 0% ~ 100% (condensing)
•
When inverter is stored under high humidity condition for long term period, it has to be dried out sufficiently
more than 1 day before connecting to the power.
CAUTION
Inverter Storage Caution
Inverters need to be sotred at the correct temperature and correct humidity.
If not, this may cause failures.
5.2 Transporting the unit to the installation location
Once it has arrived at the installation location, the inverter may be transported using the designated crane or
fork-lift. Please see below for references.
CAUTION
Impact hazard, risk of breakage to the inverter
The centre of gravity is located in the upper part of the inverter.
›
Transport the inverter in an upright position.