Page 103

Parameters

Fixed PF Mode

Figure 81: One of the example about Fixed PF

BP SERIES Inverter has a function to control the power factor. Above the figure, the red-line is apparent power,
blue-line is active power, purple-line is reactive power, and the green-dot line is power factor. If {COSPHI Reac-
tive Power Factor Internal} parameter is set to 0.8, Inverter can control the power factor as the above figure. If
apparent power exceed 1MVA by power factor, active power decreases to maintain apparent power. Fixed PF
mode is active when {COSPHI Control Mode} value is set to 2.

Tab

Number Parameter

Min

Max

Default Value

Grid

74

Reactive Power Ramp

1

30000

10sec

Controller

47

COSPHI Control Mode

0

5

2*

48

COSPHI Reactive Power Factor Internal -1

1

1

Table 24: Related Parameters (ex. BP1000 Model)

*Value for Enable of Fixed PF: 2