Fixed pf mode – KACO blueplanet 750 - 1000 kVA User Manual
Page 103

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 103
Parameters
Fixed PF Mode
Figure 81: One of the example about Fixed PF
BP SERIES Inverter has a function to control the power factor. Above the figure, the red-line is apparent power,
blue-line is active power, purple-line is reactive power, and the green-dot line is power factor. If {COSPHI Reac-
tive Power Factor Internal} parameter is set to 0.8, Inverter can control the power factor as the above figure. If
apparent power exceed 1MVA by power factor, active power decreases to maintain apparent power. Fixed PF
mode is active when {COSPHI Control Mode} value is set to 2.
Tab
Number Parameter
Min
Max
Default Value
Grid
74
Reactive Power Ramp
1
30000
10sec
Controller
47
COSPHI Control Mode
0
5
2*
48
COSPHI Reactive Power Factor Internal -1
1
1
Table 24: Related Parameters (ex. BP1000 Model)
*Value for Enable of Fixed PF: 2