KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 131

User interface

9.1.1 Digital input

The system sends digital input signal in accordance with the setting of “DI1 Select” parameter in menu of HMI
or parameter setup tool (CMT, AutoSetup).

DI1 Select

Description

Note

0

Disable DI1

1

Reserved

2

Reserved

3

Start/Stop operation of the inverter by DI1
Recognition pattern:
Stop: ∆t = 1sec
Start: ∆t = 2sec

Recognition pattern is checked whene-

ver DI1 input signal is at rising edge(T

0

)

then it is determined according to how
long the DI1 input signal has been
stayed in high state.

4

Start/Stop operation of the inverter by DI1
Recognition pattern:
Stop: ∆t = 200msec
Start: ∆t = 400msec

5

Stop operation of the inverter by DI1
Recognition pattern:
{DI1 Check Period} msec -
Stop operation

Figure 111: DI1 input signal

NOTE

The {DI1 Check Period} is parameter in ‘8.5 Digital Parameters’ that mean recognition
pattern period for inverter stop operation when selecting ‘DI1 Select’ to ‘5’.