KACO blueplanet 750 - 1000 kVA User Manual

Page 66

background image

Page 66

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Faults and Warnings

Code Message

Warning Description

Possible problem and Solution(s)

25

PEBB Over
Temp. Digital

The temperature of the heat-
sink over 100°C (Digital)

Possible problem
• PEBB Fan Failure
Solution(s)
• Inspect and if necessary clean the
heat-sink fins Change the PEBB Fan

26

Grid Phase Jump

Grid side voltage phase delay
exceed value of [Phase Jump
Theta Deadband]

Possible problem
• Grid side voltage phase delay
Solution(s)
• Check grid parameter table

27

Grid Phase Open

Grid side voltage phase open
accident

Possible problem
• Grid side one phase is open
Solution(s)
• Check the wiring connection

28

Inv. MC (PEBB 2
MC21) Failure

Inverter side contactor
(MC21 of PEBB 2) failure

Possible problem
• MC21 contactor is open
• Auxiliary switch is inoperable
Solution(s)
• Check the wiring connection
• Change the MC21

29

Inv. MC (PEBB 3
MC21) Failure

Inverter side contactor
(MC21 of PEBB 3) failure

30

Grid Over Voltage
level 1

Grid side Voltage over the
parameter [Grid Over Voltage
Level 1]

Possible problem
• The grid voltage is too high
Solution(s)
• Check the grid voltage
• Check the grid parameter

31

Grid Under Voltage
level 1

Grid side Voltage under the
parameter [Grid Under Voltage
Level 1]

Possible problem
• The grid voltage is too low
Solution(s)
• Check the grid voltage
• Check the grid parameter
• Check the MCB24

32

Grid Over Frequency
level 1

Grid side Frequency over the
parameter [Grid Over Frequency
Level 1]

Possible problem
• The grid frequency is outside the
permitted rang
Solution(s)
• Check the grid frequency
• Check the grid parameter

Table 8: Fault