KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Faults and Warnings
Code Message
Warning Description
Possible problem and Solution(s)
25
PEBB Over
Temp. Digital
The temperature of the heat-
sink over 100°C (Digital)
Possible problem
• PEBB Fan Failure
Solution(s)
• Inspect and if necessary clean the
heat-sink fins Change the PEBB Fan
26
Grid Phase Jump
Grid side voltage phase delay
exceed value of [Phase Jump
Theta Deadband]
Possible problem
• Grid side voltage phase delay
Solution(s)
• Check grid parameter table
27
Grid Phase Open
Grid side voltage phase open
accident
Possible problem
• Grid side one phase is open
Solution(s)
• Check the wiring connection
28
Inv. MC (PEBB 2
MC21) Failure
Inverter side contactor
(MC21 of PEBB 2) failure
Possible problem
• MC21 contactor is open
• Auxiliary switch is inoperable
Solution(s)
• Check the wiring connection
• Change the MC21
29
Inv. MC (PEBB 3
MC21) Failure
Inverter side contactor
(MC21 of PEBB 3) failure
30
Grid Over Voltage
level 1
Grid side Voltage over the
parameter [Grid Over Voltage
Level 1]
Possible problem
• The grid voltage is too high
Solution(s)
• Check the grid voltage
• Check the grid parameter
31
Grid Under Voltage
level 1
Grid side Voltage under the
parameter [Grid Under Voltage
Level 1]
Possible problem
• The grid voltage is too low
Solution(s)
• Check the grid voltage
• Check the grid parameter
• Check the MCB24
32
Grid Over Frequency
level 1
Grid side Frequency over the
parameter [Grid Over Frequency
Level 1]
Possible problem
• The grid frequency is outside the
permitted rang
Solution(s)
• Check the grid frequency
• Check the grid parameter
Table 8: Fault