4 grid support (cosphi control) fixed p mode – KACO blueplanet 750 - 1000 kVA User Manual
Page 102

Page 102
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
8.2.4 Grid Support (COSPHI Control)
Fixed P Mode
Figure 80: One of the example about Fixed P
BP SERIES Inverter has a function to limit active power. Above the figure, the red-line is apparent power, blue-
line is active power, purple-line is reactive power, and the green-dot line is power factor. If {Remote Power
Control} parameter is 60%, Inverter can limit the active power as the above figure. Fixed P mode is active when
{COSPHI Control Mode} value is set to from 1 to 5.
Tab
Number Parameter
Min
Max
Default Value
PV Array
22
Remote Power Control
0
100
100%
27
Remote Power Control Ramp
0
600
10sec
47
COSPHI Control Mode
0
5
2*
Table 23: Related Parameters (ex. BP1000 Model)
*Value for Enable of Fixed P: 1 ~ 5