KACO blueplanet 750 - 1000 kVA User Manual
Page 118

Page 118
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Figure 96: Grid under voltage
1. U < 0.9*U
rated
, t > 2s → Grid Under Voltage Level 1 Fault
2. U < 0.15*U
rated
, t > 150ms → Grid Under Voltage Level 2 Fault
Tab
Number Parameter
Min
Max
Default Value
Grid
3
Grid Under Voltage Level 1
75
100
90%
17
Grid Under Voltage Level 1 Trip Time
0
1
0
18
Grid Under Voltage Level 2 Trip Time
0.02
3
0.07Hz
35
Grid Under Voltage Level 2
15
100
80%
22
FRT Enable
0
1
0*
Table 33: Related Parameters (ex. BP1000 Model)
*Selection of FRT Enable
0: UV/OV Protection
1: FRT Enable