Faults and Warnings
Code Message
Warning Description
Possible problem and Solution(s)
52
Master Slave Fault
Master Slave operation Failure
Possible problem
• Wrong CAN ID
• CAN bus communication Failure
Solution(s)
• Check the parameters
• Check the CAN bus Connection
• Check the CAN bus terminal registers
57
Grid Over Frequency
Level 3
Grid side Frequency over the
parameter [Grid Over Frequency
Level 3]
Possible problem
• The grid frequency is outside the
permitted range
Solution(s)
• Check the grid frequency
• Check the grid parameter
58
Grid Under Frequency
Level 3
Grid side Frequency under the
parameter [Grid Under Fre-
quency Level 3]
Possible problem
• The grid frequency is outside the
operation range
Solution(s)
• Check the grid frequency
• Check the grid parameter
63
HMI-XCU Communi-
cation Error
HMI-XCU communication Error
Possible problem
• HMI-XCU Communication Error
Solution(s)
• Check HMI-XCU communication
connectivity
Table 8: Fault