beautypg.com

3unit description, 1 technical data – KACO blueplanet 750 - 1000 kVA User Manual

Page 9

background image

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 9

Unit Description

3

Unit Description

3.1 Technical Data

Model

BP 1000 TL3 OD DE BP 875 TL3 OD DE

BP 750 TL3 OD DE

DC Input

PV input operating voltage range

500V ~ 1000V

MPP range

550V ~ 830V

Max. permissible DC voltage (No load)

1100V

1*

Max. permissible DC current

1910A

1671A

1433A

Short-circuit current

2480A

2170A

1860A

Max. backfeed current

0A

Number of DC inputs

12 (250A fuses plus and minus)

9 (400A fuses plus and minus - Option)

AC Output

Max. output power / rated power

1000kVA / 1000kW

1000kVA / 875kW

1000kVA / 750kW

Grid voltage

3*370V (±10%)

Max. output current

1560A

Inrush current (Duration)

1315Apeak (275ms)

Maximum output fault current (Duration)

3145Apeak (870ms)

Maximum output overcurrent protection

2020A

1770A

1520A

Grid frequency

50 / 60Hz

THD of grid current

< 3% at rated power

Power factor (cos θ)

1

≥ 0.875

≥ 0.75

Power factor range

0 leading … 0 lagging (Adjustable)

Power Consumption

Internal consumption in operation

< 1% of rated power (< 2000W)

Internal consumption in stand-by

< Approx. 150W

Efficiency

Max. efficiency

98.5%

98.5%

98.5%

Euro efficiency

98.3%

98.2%

98.2%

Environmental Parameters

Operating temperature range

-20°C ~ +50°C

Storage temperature range

-20°C ~ +70°C

Relative humidity

0 ~ 100% (Condensing)

1*