3unit description, 1 technical data – KACO blueplanet 750 - 1000 kVA User Manual
Page 9

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 9
Unit Description
3
Unit Description
3.1 Technical Data
Model
BP 1000 TL3 OD DE BP 875 TL3 OD DE
BP 750 TL3 OD DE
DC Input
PV input operating voltage range
500V ~ 1000V
MPP range
550V ~ 830V
Max. permissible DC voltage (No load)
1100V
1*
Max. permissible DC current
1910A
1671A
1433A
Short-circuit current
2480A
2170A
1860A
Max. backfeed current
0A
Number of DC inputs
12 (250A fuses plus and minus)
9 (400A fuses plus and minus - Option)
AC Output
Max. output power / rated power
1000kVA / 1000kW
1000kVA / 875kW
1000kVA / 750kW
Grid voltage
3*370V (±10%)
Max. output current
1560A
Inrush current (Duration)
1315Apeak (275ms)
Maximum output fault current (Duration)
3145Apeak (870ms)
Maximum output overcurrent protection
2020A
1770A
1520A
Grid frequency
50 / 60Hz
THD of grid current
< 3% at rated power
Power factor (cos θ)
1
≥ 0.875
≥ 0.75
Power factor range
0 leading … 0 lagging (Adjustable)
Power Consumption
Internal consumption in operation
< 1% of rated power (< 2000W)
Internal consumption in stand-by
< Approx. 150W
Efficiency
Max. efficiency
98.5%
98.5%
98.5%
Euro efficiency
98.3%
98.2%
98.2%
Environmental Parameters
Operating temperature range
-20°C ~ +50°C
Storage temperature range
-20°C ~ +70°C
Relative humidity
0 ~ 100% (Condensing)
1*
1100Vdc is no-load voltage. Start-up at DC voltage is under 1000Vdc and max. operating voltage is 1000Vdc