KACO blueplanet 750 - 1000 kVA User Manual
Page 83

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 83
Parameters
Parameters
Min
Max
Unit
Descriptions
Grid Under Fre-
quency Level 3
0
3
Hz
Lower limit for grid over frequency level 3
Grid Under Fre-
quency Level 3 Trip
Time
0
30000
ms
Time for grid over frequency Level 3 trip
Upper Deadband
PPN
100
110
%
Voltage Level for activation of P/Pn function when
selected CEI 0-21 grid code
Lower Deadband
PPN
90
100
%
Voltage Level for deactivation of P/Pn function
when selected CEI 0-21 grid code
Upper Deadband
QV
10
100
%
Active Power Level for activation of Q(V) function
when selected CEI 0-21 grid code
Lower Deadband
QV
1
20
%
Active Power Level for deactivation of Q(V)
function when selected CEI 0-21 grid code
QV Voltage1
100
110
%
Voltage upper dead band of Q(V) function when
selected CEI 0-21 grid code
QV Voltage2
90
100
%
Voltage lower dead band of Q(V) function when
selected CEI 0-21 grid code
QV Voltage3
100
110
%
Voltage upper level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code
QV Voltage4
90
100
%
Voltage lower level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code
QV Inductive Max
0
48
%
Reactive Power inductive maximum value of Q(V)
function
QV Capacitive Max 0
48
%
Reactive Power capacitive maximum value of Q(V)
function
Phase Open Detec-
tion Level
0
100
%
Level of grid voltage phase open fault detection
Phase Open Trip
Time
0.1
999.9
sec
Trip time of grid voltage phase open fault detec-
tion
PJD Mode
0
2
N/A
Grid voltage phase delay fault detection mode
PJD Level
3
360
degree
Dead band of grid voltage phase delay fault
detection
PJD Trip Time
0
30000
ms
Trip time of grid voltage phase delay fault detec-
tion
Active Damping
Enable
0
2
N/A
Active damping enable
Virtual Resister
0
29.999
Ohm
Virtual register for active damping
IQ Ramp After FRT
0
30000
ms
Gating-off time after recovering from low voltage
accident
Table 12: Grid Parameters