KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Page 83

Parameters

Parameters

Min

Max

Unit

Descriptions

Grid Under Fre-
quency Level 3

0

3

Hz

Lower limit for grid over frequency level 3

Grid Under Fre-
quency Level 3 Trip
Time

0

30000

ms

Time for grid over frequency Level 3 trip

Upper Deadband
PPN

100

110

%

Voltage Level for activation of P/Pn function when
selected CEI 0-21 grid code

Lower Deadband
PPN

90

100

%

Voltage Level for deactivation of P/Pn function
when selected CEI 0-21 grid code

Upper Deadband
QV

10

100

%

Active Power Level for activation of Q(V) function
when selected CEI 0-21 grid code

Lower Deadband
QV

1

20

%

Active Power Level for deactivation of Q(V)
function when selected CEI 0-21 grid code

QV Voltage1

100

110

%

Voltage upper dead band of Q(V) function when
selected CEI 0-21 grid code

QV Voltage2

90

100

%

Voltage lower dead band of Q(V) function when
selected CEI 0-21 grid code

QV Voltage3

100

110

%

Voltage upper level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code

QV Voltage4

90

100

%

Voltage lower level to calculate ramp of Q(V)
function when selected CEI 0-21 grid code

QV Inductive Max

0

48

%

Reactive Power inductive maximum value of Q(V)
function

QV Capacitive Max 0

48

%

Reactive Power capacitive maximum value of Q(V)
function

Phase Open Detec-
tion Level

0

100

%

Level of grid voltage phase open fault detection

Phase Open Trip
Time

0.1

999.9

sec

Trip time of grid voltage phase open fault detec-
tion

PJD Mode

0

2

N/A

Grid voltage phase delay fault detection mode

PJD Level

3

360

degree

Dead band of grid voltage phase delay fault
detection

PJD Trip Time

0

30000

ms

Trip time of grid voltage phase delay fault detec-
tion

Active Damping
Enable

0

2

N/A

Active damping enable

Virtual Resister

0

29.999

Ohm

Virtual register for active damping

IQ Ramp After FRT

0

30000

ms

Gating-off time after recovering from low voltage
accident

Table 12: Grid Parameters