Page 31
Storage/Installation/Start-up
5.5.4 Connection for the PV generator (DC connection)
The DC connection is located in the left side of the housing, at the bottom.
Connection data
Tightening torque for DC terminal connections
43Nm
Max. Cable diameter for each fuse
240mm
2
x 2
Cable lug hole size
12mm ~ 14mm
Fuse protection for DC connection
Up to 250A, 1100V
12 fuses each for DC+ / DC-
Option (400A)
Tightening torque for DC terminal connections
43Nm
Max. Cable diameter for each fuse
300mm
2
x 2
Cable lug hole size
12mm ~ 14mm
Fuse protection for DC connection
Up to 400A, 1100V
9 fuses each for DC+ / DC-
DANGER
Lethal voltages in the PV system
Lethal voltages are present in the PV system.
›
Make absolutely sure that the + and – are properly insulated.