2 rs485 interface – KACO blueplanet 750 - 1000 kVA User Manual
Page 133

KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Page 133
User interface
9.2 RS485 interface
The inverter has two RS485 connections.
RS485-1
Interface for the Powador Argus
Interface for optional Powador-go
RS485-2
Interface for the HMI’s internal data logger, or for the external Powador proLOG data logger
9.2.1 RS485-1 Interface
1d
1c
2d
2c
3d
3c
4d
4c
5d 6d 7d 8d
5c 6c 7c 8c
1c
PE
1d
PE
R
S4
85
2d
5d
2c
5c
3d
6d
3c
6c
4d
7d 8d
4c
7c 8c
Signal transceiver
A B GND
Figure 114: RS485-1 connection
Figure 115: Circuit diagram for RS485-1
connection
Terminal number
Terminal designation
Specification
Wire cross- section
1c
RS485 A1
RS485 signal A1
AWG22
(0.326mm
2
)
1d
RS485 B1
RS485 signal B1
3c
RS485 C1
Termination resistor
terminal
3d
RS485 G1
RS485 data transmission
GND 1
"
For termination disposal, you can use RS485 B1(1d) and RS485 C1(3c) with jumper because
termination resistor is already installed inside of XCU board.
Table 38: Connections for RS485-1