KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0

Parameters

8.1 Parameters

PV Array Parameters

Parameters

Min

Max

Unit

Descriptions

MPPT Enable

0

1

-

1: MPPT is enabled
0: MPPT is disabled

MPPT V Maximum

0

830

V

dc

Maximum voltage to run MPPT

MPPT V Start

200

800

V

dc

MPPT wake-up voltage

MPPT T Start

0

3600

sec

Time delay for MPPT wake-up

MPPT P Stop

0

10000

W

Disconnect inverter from Grid when PV output
power is lower than the setting value of {MPPT P
Stop}

MPPT T Stop

0

600

sec

Time delay while inverter decides if PV output
power is lower than the setting value of {MPPT P
Stop}

MPPT V Minimum

200

800

V

dc

Minimum voltage to run MPPT
Exception)

DC OverVoltage
Level

300

1020

V

dc

Upper limit for PV over voltage fault

DC OverCurrent
Level

0

150

%

Upper limit for PV over current fault

MPP Factor

0

1

-

Maximum power point factor

MPP Range Upper

10

300

V

dc

Upper limit of maximum power point

MPP Range Lower

10

300

V

dc

Lower limit of maximum power point

PV Operation Level 900

1020

V

dc

Maximum PV operation level

PD Over DC V

Mode

0

1

-

Inverter output reduction in the DC input voltage
range from [MPPT V Maximum] to [PV Operation
Level]
0: Disable
1: Enable

Ground Type

0

2

-

PV side Grounding Type
0: Isolation Type
1: Negative Type
2: Positive Type

PV Power Check

Time

0

3600

sec

Inverter operation mode is changed if PV output
power is lower than the setting value of {MPPT P
Stop} during time delay of {PV Power Check Time}
(When {RPO Enable} is ‘1: Enable’)

Table 10: PV Array Parameters