Operation mode – KACO blueplanet 750 - 1000 kVA User Manual
Page 124

Page 124
KACO blueplanet 1000/875/750 TL3 M1 IS OD DEX0
Parameters
Operation Mode
COSPHI Control operates in RPC (Remote Power Control) and internal modes according to communication
status to control power with Fixed COSPHI and Fixed Q.
Figure 103: Transition of RPC mode and Internal Mode
1. RPC mode
While HMI is modifying XCU’s {Remote Power Control}, {COSPHI RPC Reactive Power} and {COSPHI RPC Power
Factor} parameters with two-minute interval, COSPHI Control operates in RPC mode. In RPC mode, it operates
according to {Remote Power Control}, {COSPHI RPC Reactive Power}, and {COSPHI RPC Power Factor} modes.
2. Internal mode
If RPC mode parameter such as {Remote Power Control}, {COSPHI RPC Reactive Power}, and {COSPHI RPC
Power Factor} is not be modified within five minutes, XCU will operate in Internal mode. In Internal mode,
COSPHI control operates according to internal mode parameters such as {COSPHI Internal Reactive Power} and
{COSPHI Internal Power Factor}, {Remote Power Control} parameter does not influence on the active power.