Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 59

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 58 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
58
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault
No
.
Fault Legend
Description
1760B
95755
30219
Alm:Memobus
Comm
CE – Communication fault. Control
data was not received for 2 seconds
after initial communication.
Yes
Yes
Yes
Minor
Minor
This is a serial communications error.
If h5-05=1, then the alarm bit will be
set if no serial communication is seen
AND h5-04= 3. Check validity of
Smart Trac AC1 CPU card firmware
and application program.
1760C
95756
30220
Alm:Mtr Overlded
OL1 – Motor overload. Protects the
motor. Motor thermal overload
protection has tripped. Inverter
parameter L1-02 has been exceeded
(initial value: 150% for 60 sec.).
Yes
Yes
Yes
Minor
Minor
Alarm is declared if thermal overload
exceeds 90% of fault detection level
AND L1-01= 1. Load may be too
large. Check drive capacity (inverter
parameter o2-04) for correct factory
setting. Check for proper setting of
electronic thermal overload setting:
inverter parameters E1-02, E2-01,
L1-02. Try disconnecting motor
wiring from output terminals – if OL
is still indicated, problem may be due
to noise or faulty inverter cards
1760D
95757
30221
Alm:Inv Overlded
OL2 – Drive overload. Protects the
Smart Trac AC1 drive. Drive
overload protection has tripped.
Yes
Yes
Yes
Minor
Minor
See fault “Motor Overloaded” for
details.