Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 26

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 25 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
25
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
12B06
76550
11014
NDelay Input
An NDelay function block has
detected that its “Delays” input is
outside the valid range of 1 to 500.
No
Yes
Yes
Minor
FB_se
tup
Review the NDelay function blocks to
ensure all “Delays” inputs are within the
range of 1 to 500.
12B07
76551
11015
REFQ Input
A REFQ function block has detected
a “CascadeNumber” input >
“MaxCascadeNumber” input, or,
“MaxCascadeNumber” input does
not fall within a valid range of 1
through 255.
No
Yes
Yes
Minor
FB_se
tup
Ensure the REFQ function block has a
“CascadeNumber” input less than or
equal to “MaxCascadeNumber” input.
Ensure “MaxCascadeNumber” input
ranges from 1 to 255.
12B08
76552
11016
DIAM_2
Input
A DIAM_2 block has detected an out
of range value on one or more of its
inputs labeled RatedLineSpeed,
S_RPM_AT_M_RPM,
MaxDiameter, MinDiameter, or
NumberCalculation.
No
Yes
Yes
Minor
FB_se
tup
Ensure the DIAM_2 block has the proper
values at its inputs as follows:
RatedLineSpeed > 0,
S_RPM_AT_M_RPM > 0,
MinDiameter > 2 inches, or 5 cm,
MinDiameter <= MaxDiameter <= 99
inches, or 200 cm,
0 <= NumberCalculation <= 255.
12B09
76553
11017
INRT_1 Input
An INRT_1 block has detected a
value of 0 on the RatedHorsepower
input.
No
Yes
Yes
Minor
FB_se
tup
Ensure the INRT_1 block has a positive,
non-zero value for its RatedHorsepower
input.
12B0A
76554
11018
CTCW_0
Input
A CTCW_0 block has detected a
value of 0 on its Diameter input
No
Yes
Yes
Minor
FB_se
tup
Ensure the CTCW_0 block has a
positive, non-zero value for its Diameter
input.
12B0B
76555
11019
CTCW_1
Input
A CTCW_1 block has detected a
value of 0 on either the Horsepower
or the S_RPM_AT_M_RPM inputs.
No
Yes
Yes
Minor
FB_se
tup
Ensure that the CTCW_1 block has
positive, non-zero values for both the
Horsepower and S_RPM_AT_M_RPM
inputs.