Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault
No
.
Fault Legend
Description
value outside the permitted
range.
03- Terminal. Multi-function input
setting fault.
05- Sequence Select. Option card
selection fault.
06- PG Opt Missing. PG card not
installed.
07- Analog Selection. Multi-
function analog input selection
fault.
08- Terminal. Selection parameter
fault. A parameter has been
changed that is not available in
the present control method.
10- V/F Ptrn Setting. V/f data
setting fault.
11- CarrFrq/ON-Delay. Carrier
frequency parameter(s) set out
of range.
source is set for option card
(Smart Trac.AC1 CPU card) i.e.
B1-01, B1-02 = 3, but no option
card is connected.
06- Control method set to flux vector
or V/F with PG, and no PG card
is installed.
07- Both multi-function analog
inputs on the inverter card, H3-
05 and H3-09, have been
programmed for the same data
(except 1F).
08- May be trying to change an
inverter parameter that is not
available in closed loop vector
mode.
10- Occurs when the custom V/f
pattern does not meet the
following criteria: inverter
parameters E1-04 > E1-06 > E1-
07 > E1-09.
11- Occurs when the carrier
frequency inverter parameters
are set as follows: C6-01 > 5
kHz and C6-02 < 5 kHz; C6-03
> 6 and C6-01 < C6-02.
17561
95585
30049
Not used