Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
27
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
12B5F
76639
11103
Rev
Overspeed
The TMON block has detected an
overspeed condition in the reverse
direction.
Yes
Yes
Yes
Minor
Major
Motor speed has exceeded the reverse
setpoint: TachometerInput <
(RevOverspeedLimit / 100). Reduce
commanded speed or load if runaway
condition exists.
12B60
76640
11104
TENR Input
A TENR function block has detected
a value of zero for any one of these
inputs: TensionZoneLength,
WebWidth, WebThickness, or
YoungsModulus.
No
Yes
Yes
Minor
FB_se
tup
Ensure that the TENR function block has
non-zero values at TensionZoneLength,
WebWidth, WebThickness or
YoungsModulus inputs. Note that a
function block uses a value of ‘0’ when
an input is left unconnected.
12B61
76641
11105
SCRV Input
A SCRV function block has detected
a negative value for one of these
inputs: Accel_Time, Decel_Time,
Accel_Jrk_Percent,
Decel_Jrk_Percent.
No
Yes
Yes
Minor
FB_se
tup
Ensure that the SCRV block has
Accel_Time, Decel_Time,
Accel_Jrk_Percent, and
Decel_Jrk_Percent input values are
greater than or equal to zero.
12B62
76642
11106
DAVE Input
A DAVE function block has detected
an out of range value at its
“NumberOfSamples” input.
No
Yes
Yes
Minor
FB_se
tup
Ensure that the DAVE function blocks
use values from 1 to 500 at their
“NumberOfSamples” inputs.