Stlan driver, Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 34

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 33 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
33
5.2 STLAN Driver
The following section details fault numbers assigned to Smart Trac AC1 Local Area Network (ARCNET).
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
14EE8
85736
20200
LAN Hardware
Flt
LAN hardware fault.
Yes
Yes
Yes
Minor
Major
ARCNET card is defective or not installed
properly.
14EE9
85737
20201
LAN Max Tx Flt
LAN - max number of
transmit attempts
exceeded.
No
Yes
Yes
Minor
Minor
Attempting to transmit LAN messages to a
channel or node that isn’t active or doesn’t
exist.
14EEA
85738
20202
LAN Illegal Msg
LAN - illegal message
type.
No
Yes
Yes
Minor
Minor
Message is not supported by STLAN
Interface Card.
14EEB
85739
20203
LAN Missed
Bcast
LAN missed a
broadcast message.
No
Yes
Yes
Minor
Minor
Excessive amount of LAN traffic. Reduce
number of messages being sent/received.
May have too many nodes on the network –
use an ARCNET active hub to buffer
messages.
14EEC
85740
20204
LAN Missed
Dirct
LAN missed a directed
message.
No
Yes
Yes
Minor
Minor
Excessive amount of LAN traffic. Reduce
number of messages being sent/received.
May have too many nodes on the network –
use an ARCNET active hub to buffer
messages.
14EED
85741
20205
LAN No Tx
Room
LAN - no room to
transmit message.
No
Yes
Yes
Minor
Minor
Excessive amount of LAN traffic. Reduce
number of messages being sent/received.
14EEE
85742
20206
LAN No Rx
Room
LAN - no room to
receive message.
No
Yes
Yes
Minor
Minor
Excessive amount of LAN traffic. Reduce
number of messages being sent/received.