Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

53

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

1758A

95626

30090

OPE10 Fault

V/F Ptrn Setting. V/f data setting
fault.

Yes

Yes

Yes

Minor

Major

Occurs when the custom V/f pattern
does not meet the following criteria:
inverter parameters E1-04 > E1-06 >
E1-07 > E1-09.

1758B

95627

30091

OPE11 Fault

CarrFrq/ON-Delay. Carrier
frequency parameter(s) set out of
range.

Yes

Yes

Yes

Minor

Major

Occurs when the carrier frequency
inverter parameters are set as
follows: C6-01 > 5 kHz and C6-02 <
5 kHz; C6-03 > 6 and C6-01 < C6-
02.

1758C –

175F7

95628 –

95735

30092

30199

Not used

175F8

95736

30200

Alm:Undervoltage

UV – Main circuit undervoltage.
Occurs 2 seconds after detection of
low voltage. Detection levels:
190VDC for 230V rated unit;
380VDC for 460V rated unit;
546VDC for 600V rated unit.

Yes

Yes

Yes

Minor

Minor

Check input AC supply. Possibility
of erroneous operation due to noise:
remove noise source by connecting
surge suppressor to relay and
magnetic contactor coils; provide line
filter to remove noise on input power
line. Possibility of gate drive PCB is
faulty. Note: alarm is declared only if
drive is NOT in Run mode.