Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 24

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 23 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
23
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
12AFE
76542
11006
PG Card ID
Error
The PG card can’t be found. This is
due to the software not seeing the
correct identification code on the PG
card.
Yes
Yes
Yes
Minor
Major
The correct PG card must be installed for
the Smart Trac AC1 function blocks
used.
12AFF
76543
11007
PG A/D
Retries
The PG_ANALOG_IN function
block senses that the PG card has not
done an analog to digital conversion
in the allotted time after the number
of attempts set by the TriesB4Fault
input to the PG_ANALOG_IN
block.
No
Yes
Yes
Minor
Minor
Try increasing the number of attempts
for conversion, TriesB4Fault, to a higher
value. Possibility the PG card is
defective.
12B00
76544
11008
I/O Memory
Alloc
Dynamic RAM was not available for
use by one or more Function Blocks.
Yes
Yes
Yes
Minor
Major
These Function Blocks require use of
DRAM: CAVE, LDelay, NDelay, and
REFQ. One of these FBs was unable to
allocate memory to support its function.
Recycle power to Smart Trac AC1. If
problem persists, replace Smart Trac
CPU card.