Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 27

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 26 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
26
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
12B0C
76556
11020
PG_TACH
Input
A PG_TACH or PG_TACH2 block
has detected a value of 0 on the
TachCounts or RatedSpeed inputs.
No
Yes
Yes
Minor
FB_se
tup
Ensure the PG_TACH or PG_TACH2
block has non-zero values for the
TachCounts and RatedSpeed inputs.
12B0D
to
12B5B
76557 to
76635
11021
to
11099
Not Used
12B5C
76636
11100
Tach Loss
The TMON block has detected a
tachometer (encoder) loss.
Yes
Yes
Yes
Minor
Major
Check wiring from encoder to PG card.
Tach loss occurs when AuxSpeedSense
> (AuxSenseLevel / 100) and
TachometerInput < (TachSenseLevel /
100).
12B5D
76637
11101
Reverse Tach
Flt
The TMON block has detected a
reversed tachometer (encoder)
connection.
Yes
Yes
Yes
Minor
Major
Change wiring from encoder to PG card.
Declared when AuxSpeedSense >
(AuxSenseLevel / 100) AND
(ReferenceInput > 0 and
TachometerInput < 0) OR
(ReferenceInput < 0 and
TachometerInput > 0).
12B5E
76638
11102
Fwd
Overspeed
The TMON block has detected an
overspeed condition in the forward
direction.
Yes
Yes
Yes
Minor
Major
Motor speed has exceeded the forward
setpoint: TachometerInput >
(FwdOverspeedLimit / 100). Reduce
commanded speed or load if runaway
condition exists.