Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
19
Displayed Fault No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
Fault Legend
Description
7FFE
32766
Watchdog
Timeout
One or more Program Units
associated with a Task have not
been completed within the
‘Watch Dog Timeout’ setting.
Yes
Yes
Yes
Critical
Critical
and
Major
Extend the Watchdog Timeout for the faulted
Task. Generally, do not exceed 3x the cyclic
task’s value nor 300ms for an IoSync Task.
Application program may be overburdened –
reduce amount of logic placed in fast Tasks
(15ms or faster) to slow Tasks (30ms or slower).
This may include reducing number of Program
Units and/or program elements.
7FFF
32767
Fatal Error
Unrecoverable fault, usually
occurs during Driver startup.
Yes
Yes
Yes
Critical
Critical
and
Major
Verify that there are no hardware problems on
the PC used to create the application. Re-
compile and reload the program and reload it to
the SmartTrac drive. The Smart Trac main CPU
card may be faulty. If available, download a
small test program to see if fault persists.