Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
24
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
12B01
76545
11009
TAPER Setup
Flt
The TAPER block declares this fault
if input Tension Setpoint < 0, or
input Taper Ratio <=0, or input
Present Diameter <=0, or input Core
Diameter <= 0, or input Full Roll
Diameter <= input Core Diameter, or
input RatioAt20Percent_BU <=0, or
input RatioAt40Percent_BU <=0, or
input RatioAt60Percent_BU <=0, or
input RatioAt80Percent_BU <=0, or
input RatioAt100Percent_BU <= 0.
No
Yes
Yes
Minor
FB_se
tup
Change application program to meet the
following:
Tension Setpoint > 0,
Taper Ratio > 0,
Present Diameter > 0,
Core Diameter > 0,
Full Roll Diameter > Core Diam,
RatioAt20Percent_BU > 0,
RatioAt40Percent_BU > 0,
RatioAt60Percent_BU > 0,
RatioAt80Percent_BU > 0,
RatioAt100Percent_BU > 0.
12B02
76546
11010
PG_DELTA_
P ID
The PG Delta card can’t be found.
This is due to the software not seeing
the correct identification code on the
PG card which is used for
registration applications.
Yes
Yes
Yes
Minor
Major
The correct PG card must be installed for
the Smart Trac PG_DELTA_P function
block used.
12B03
76547
11011
PG_DELTA_
P Setup
The PG_DELTA_P function block
declares this fault when the counter
start and stop source inputs are not in
the range from 1 to 4.
No
Yes
Yes
Minor
Minor
Change input value(s) to counter start
input and stop source such that they fall
within the range of 1 through 4.
12B04
76548
11012
FGEN5 Input
The FGEN5 block declares this fault
if input X_At_X5 is set to a value
less than or equal to input X_At_X0.
No
Yes
Yes
Minor
FB_se
tup
Set inputs such that
X_At_X5 > X_At_X0.
12B05
76549
11013
LDelay Input
An LDelay function block has
detected that its “Delays” input is
outside the valid range of 1 to 500.
No
Yes
Yes
Minor
FB_se
tup
Review the LDelay function blocks to
ensure all “Delays” inputs are within the
range of 1 to 500.