Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 56

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 55 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
55
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault
No
.
Fault Legend
Description
175FD
95741
30205
Alm:Ovrtrq Det 2
OL4 – Overtorque detect 2 alarm.
Output current exceeded Overtorque
Detection Level 2 set in inverter
parameter L6-05. For V/F control,
parameter L6-05 is considered to be
Output Current.
Yes
Yes
Yes
Minor
Minor
The input labeled ‘Minor’ is set only
if L6-01 = 1 or 2. Reduce load,
increase acceleration time, or
increase inverter parameter setting
L6-02.Reduce load, increase
acceleration time, or increase inverter
parameter setting L6-05.
175FE
95742
30206
Alm:External Flt
Both FWD and RUN commands are
simultaneously input for 500ms or
longer.
Yes
Yes
Yes
Minor
Minor
Check input wiring to ensure that
FWD and REV are mutually
exclusive.
175FF
95743
30207
Alm: BB Circuit
Base Block activated by external
contact into terminal programmed
for base block.
Yes
Yes
Yes
Minor
Minor
Note: Assuming one of the input
terminals is programmed for external
BB and the BB is being asserted by
an external contact, an overspeed or
max overheat of drive will cause
inverter BB of signals to the power
devices. Recycle SmartTrac AC1
power. If problem persists, replace
inverter card.
17600
95744
30208
Alm: Ext Fault 3
EF3 – External fault signal at
terminal 3 of the inverter card. This
can be programmed to be N.O. or
N.C. contact.
Yes
Yes
Yes
Minor
Minor
Fault has occurred in circuits outside
the Smart Trac AC1 inverter card.
Troubleshoot and correct. Alarm
declared only if H1-01 is in the
range of 2Ch to 2Fh.