Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 19

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 18 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
18
Displayed Fault No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
Fault Legend
Description
7FF9
32761
No Startup FB
No startup function block was
configured for a user task.
Yes
Yes
Yes
Critical
Critical
and
Major
Verify that there are no hardware problems on
the PC used to create the application. Re-
compile and reload the program and reload it to
the SmartTrac drive. The Smart Trac main CPU
card may be faulty. If available, download a
small test program to see if fault persists..
7FFA
32762
Breakpoint Set
Breakpoint encountered in
program. Not really a fault but
used for debug purposes.
Yes
Yes
Yes
N/A
Critical
and
Major
Verify that there are no hardware problems on
the PC used to create the application. Re-
compile and reload the program and reload it to
the SmartTrac drive. The Smart Trac main CPU
card may be faulty. If available, download a
small test program to see if fault persists.
7FFB
32763
Bad Offset
Range
Attempt to address data within
memory is out of range.
Yes
Yes
Yes
Critical
Critical
and
Major
Verify that there are no hardware problems on
the PC used to create the application. Re-
compile and reload the program and reload it to
the SmartTrac drive. The Smart Trac main CPU
card may be faulty. If available, download a
small test program to see if fault persists.
7FFC
32764
Task Overrun
Task has taken too long to
complete. Applies to Cyclic and
IoSync Tasks only.
Yes
Yes
Yes
Critical
Critical
and
Major
Application program may be overburdened –
reduce amount of logic placed in fast Tasks
(15ms or faster) to slow Tasks (30ms or slower).
This may include reducing number of Program
Units and/or program elements.
7FFD
32765
Restart Failed
A request to have a Task change
from stop to start mode has
failed.
Yes
Yes
Yes
Critical
Critical
and
Major
Check for valid installed hardware. For example,
if using the STLAN driver, make sure an
ARCNET card is part of the Smart Trac card
stack.