Smart trac, Faults.doc – Yaskawa SmartTrac Fault Tables User Manual
Page 58

10/17/00
New Berlin
Technology Center
Smart Trac
Product
Development
Design
Document
Faults.doc
Rev. # 19
Page 57 of 64
Title: Fault Declarations
The information contained in this document is the
CONFIDENTIAL
property of
MagneTek Inc.
File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC
Print Date: 10/17/00
57
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault
No
.
Fault Legend
Description
17607
95751
30215
Alm: Overspd Det
OS – Motor overspeed alarm. Motor
speed exceeded overpspeed level set
by inverter parameters F1-08, F1-
09.
Yes
Yes
Yes
Minor
Minor
Check for correct tach (encoder) PPR
value in inverter parameter F1-01.
May have excessive noise on encoder
signal inputs to Smart Trac AC1
drive. Consult MagneTek about
specifications of user-supplied
encoder. Alarm declared only if
inverter parameter F1-03 = 3.
17608
95752
30216
Alm: Spd Deviatn
DEV – Speed deviation alarm.
Difference between speed reference
and speed feedback exceeded the
deviation level set in inverter
parameters F1-10, F1-11.
Yes
Yes
Yes
Minor
Minor
Decrease load, increase
acceleration/deceleration times, or
increase deviation levels found at
inverter parameters f1-10, f1-11.
Alarm declared if f1-04 = 3. The
input labeled ‘Minor’ is active only if
a1-02 = 1 or 3, AND d5-01 = 0.
17609
95753
30217
Alm: PG Open
PGO – Alarm; No tach pulses
received when speed reference > 0
in time set by f1-14. This is the
same as a Tach Loss fault.
Yes
Yes
Yes
Minor
Minor
Check wires from the Smart Trac
AC1 PG card to encoder, faulty tach,
faulty tach power supply or look for
damaged wires. The alarm is
declared only if inverter parameters
a1-02 = 1 or 3, and d5-01= 0, and f1-
02= 3
1760A
95754
30218
Alm: Oper Disc
OPR – Operator disconnected.
Digital operator has been
disconnected from drive while in
Run mode.
Yes
Yes
Yes
Minor
Minor
Reconnect digital operator to
inverter. Alarm is declared if o2-06=
0.