4. Function Blocks
The following section details fault numbers assigned to C language function blocks.
Displayed Fault
No.
Priority
D
is
p
lay?
Newest
List
?
Ol
d
es
t
List
?
Severity
Assig
n
Program
Input
Corrective Action
Control
Node
Monitor
Fault
Manager
In
ternal Fault #
Fault Legend
Description
12AF8
76536
11000
No System
Clock
A ‘C’ language function block
(WEBB or DIAM_0) has made a
system call to get the present time
and the call returned indicating that
the time was not available. This
fault is declared by blocks that need
to know the present relative time to
perform their function.
No
Yes
Yes
Minor
Minor
Some incompatibility may be happening
with the version of the operating system
and the downloaded program. The CPU
card may be defective.
12AF9
76537
11001
Web Break
The WEBB block has declared a web
break.
Yes
Yes
Yes
Minor
Major
Check web material for breakage or look
at logic output for same, and repair if
necessary.
12AFA
76538
11002
Ilegal Scan
Time
Either the RAMP, RAMP_1, SCRV
or SPDR_1 block has an illegal scan
time.
Yes
Yes
Yes
Minor
Major
The RAMP and RAMP_1 block cannot
operate with a scan time of less than
0.002 seconds; the SCRV block cannot
operate with a scan time of less than
0.0005 seconds. The SPDR_1 block
must have a scan time > 0.