4.2

TROUBLESHOOTING BY ALARM CODES (Cent’d)

4.2.21 ALARMS 3301 TO 3305 (OVERCURRENT)

Table 4.23

Alarms 3301

3305

Causeof Trouble

Control board fault

Current feedback
circuit error

Main circuit
transistor module
error

Motor grounding

Check Method

Solution

Alarm occurs immediately after control power

Replace

is turned ON.

Alarm occurs after main power is turned ON.

Replace

MCCB is not tripped.

SERVOPACK.

Alarm occurs after main power is turned ON.

Replace
SERVOPACK.

Alarm occurs after main power is turned ON.

Replace motor.

MCCB is

4.2.22 ALARMS 3311 TO 3315

TRIP)

Table 4.24

Alarm

to 3315

Trip)

Causeof Trouble

Check Method

Solution

Control board fault

Main circuit
thyristor-diode
m o d u l e e r r o r

MCCB failure

Alarm occurs immediately after control power
is turned ON.

Alarm occurs after main power is turned ON.

Replace

SERVOPACK.

Replace
SERVOPACK.

Alarm occurs after main power is turned ON.

Replace
SERVOPACK.

4.2.23 ALARMS 3321 TO 3325 (REGENERATIVE

Table 4.25

3321 to 3325 (Regenerative Error)

Causeof Trouble

Control board fault

Regenerative

error

Wire break in
regenerative resistor

Check Method

Alarm occurs immediately after control power
is turned ON.

Alarm occurs 0.5 to 1 second after main power
is turned ON. MCCB is not tripped.

Alarm occurs after main power is turned ON.

Solution

SERVOPACK.

Replace
SERVOPACK.

Replace SERVOPACK.
Check regenerative
resistor and replace
if necessary.