4 network settings, Prerequisite, Adjusting the network settings – HEIDENHAIN iTNC 530 (340 49x-01) User Manual
Page 641: 4 netw or k set tings 15.4 network settings
![background image](https://www.manualsdir.com/files/816209/content/doc641.png)
HEIDENHAIN iTNC 530
641
15.4 Netw
or
k Set
tings
15.4 Network Settings
Prerequisite
Adjusting the network settings
The iTNC 530 is shipped with two network connections: The Local
Area Connection and the iTNC Internal Connection (see figure at
right).
The Local Area Connection is the iTNC’s connection to its network.
You may adjust all familiar Windows 2000 settings to your network
(also see the Windows 2000 network description).
You must log on as a local administrator to be able to
change the network settings. Please contact your machine
tool builder for the required user name and password.
The network should be configured only by network
specialists.
The iTNC Internal Connection is exactly that: an internal
iTNC connection. The configuration of this connection
must not be changed. Changes might cause the iTNC to
stop functioning.
This internal network address has a default setting of
192.168.254.253
and must not collide with your company
network, meaning that the subnet 192.168.254.xxx
cannot already exist in your network.
The option Obtain IP address automatically must be
inactive.