Appendix C Use of Basic Instructions|DOP-EXIO Series

Revision March, 2008, Doc. Name: 2007PDD23000014

C-9

Program Example:
Ladder diagram:

Instruction code: Operation:
LD

X0

Loading in A contact of X0

MC

N0

Enabling N0 common series connection
contact

LD

X1

Loading in A contact of X1

OUT Y0 Driving

Y0

coil

:

LD

X2

Loading in A contact of X2

MC

N1

Enabling N1 common series connection
contact

LD

X3

Loading in A contact of X3

OUT Y1 Driving

Y1

coil

:

MCR

N1

Disabling N1 common series connection
contact

:

MCR

N0

Disabling N0 common series connection
contact

:

LD

X10

Loading in A contact of X10

MC

N0

Enabling N0 common series connection
contact

LD

X11

Loading in A contact of X11

OUT Y10 Driving

Y10

coil

:

MCR

N0

Disabling N0 common series connection
contact

X0

Y0

MC

N0

X1

X2

Y1

MC

N1

X3

MCR

N1

MCR

N0

X10

MC

N0

Y10

X11

MCR

N0

Mnemonic Functions

LDP

Rising-edge Detection Operation

X0~X17 Y0~Y17

M0~M1279

S0~S127

T0~T127 C0~C254

D0~D599

Operand

9

9

9

9

9

9

-

Explanations:
The method of using LDP is the same as using LD, but the actions of the two instructions differ. LDP
saves the current content and store the detected status of rising-edge to the accumulative register.

Program Example:
Ladder diagram:

Instruction code:

Operation:

LDP

X0

Starting X0 rising-edge detection

AND

X1

Series connecting A contact of X1

X0

X1

Y1

OUT Y1

Driving

Y1

coil