beautypg.com

Delta Electronics Extension Digital I/O Module DOP-EXIO14RAE User Manual

Page 152

background image

Appendix D Use of Application Instructions|DOP-EXIO Series

Revision March, 2008, Doc. Name: 2007PDD23000014

D-71

Mnemonic

Operands Function

LD

D

S

1

S

2

Contact Logical Operation LD※

Bit Devices

Word Devices

X Y M S K H

KnX

KnY

KnM KnS

T

C

D

E

F

S

1

S

2

y

Note: :

=

, >, <, <>, ≦, ≧

16-bit instruction (5 Steps)

LD※

Continuous
execution

- -

32-bit instruction (9 Steps)

DLD※

Continuous
execution

- -

y

Flags: None

Operands:

S

1

: Data source device 1

S

2

: Data source device 2

Explanations:
1. This instruction compares the content in S

1

and S

2

. If the result is not “equal”, the continuity of

the instruction is enabled. If the result is “equal”, the continuity of the instruction is disabled.

2. LD※ (=, >, <, <>, ≦, ≧) instruction is used for direct connection with BUS.

16 -bit instruction

32 -bit instruction

Continuity condition

No-continuity

condition

LD=

D

LD=

S

1

S

2

S

1

S

2

LD>

D

LD>

S

1

S

2

S

1

S

2

LD<

D

LD<

S

1

S

2

S

1

S

2

LD<>

D

LD<>

S

1

S

2

S

1

S

2

LD<=

D

LD<=

S

1

S

2

S

1

S

2

LD>=

D

LD>=

S

1

S

2

S

1

S

2

3. If the most left bit of S

1

and S

2

(16-bit instruction: b15、32-bit instruction: b31) is “1”, the compare

value will be regarded as the negative value for comparison.

4. When 32-bit counters (C200 ~) are used in this instruction for comparison, make sure to adopt

32-bit instruction (DLD※). If 16-bit instructions (LD※) is adopted, a “program error” will occur
and the ERROR indicator on the panel will flash and the connecting controller can not run..

Program Example:
1. When the value of C0 is equal to the value of K200, Y10 = On.
2. When the value of D200 is higher than -29 and X1 = On, Y11 = On will be retained.
3. When the value of C200 is lower than 678,493 and M3 = On, M50 = On.