beautypg.com

Power reset external adjustment, Power reset external adjustment -2 – Gasboy Atlas Fuel Systems Installation Manual User Manual

Page 76

background image

Start-up for Atlas Mechanical Series

Power Reset External Adjustment

Page 9-2 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014

Power Reset External Adjustment

If the pump or remote dispenser unit fails to reset or shut off properly, the reset motor must be
adjusted. To adjust the reset motor, proceed as follows:

1

Loosen the lock nut on the adjusting screw and back the screw out until it stops.

2

Move the reset lever to the ON position.

3

Turn the adjustment screw in until the reset motor starts.

4

Advance the adjustment screw an additional 1/2 to 3/4 turn. Hold the screw in this position and
tighten the lock nut.

5

Move the reset lever to the OFF position, and then back to the ON position to ensure that the
reset motor operates properly. The reset coupling must make one revolution and stop.

Figure 9-1: Power Reset for Pump or Remote Dispenser Unit

Adjustment Screw

Lock Nut