MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014

Page 3-1

Classifying Hazardous Locations

Hazardous Locations

3 – Hazardous Locations

Classifying Hazardous Locations

Any activity (such as smoking or drilling) that can cause an explosion must be done well
outside the vapor area.

Figure 3-1

is based on National Fire Protection Association (NFPA) 30A and NFPA 70

®

.

Figure 3-1: Hazardous Locations Diagram

20'

20'

20'

*DEF dispensers located outside the 20 feet area are unclassified.
Notes: 1) Not applicable to DEF-only dispensers.

2) DEF is not flammable and does not generate explosive vapors. For any requirements, consult local regulatory agencies. For

example, units dispensing DEF and diesel must follow the flammable fuel regulatory requirements.

20’

18”

Unclassified

18”

Vapor Barrier

20’

DEF

18”

18”

18”

48”

Division 1

Division 2

Division 2

Division 2*

18”

18”

18”

Division 1

Division 2

Dispenser Without Vapor
Barrier Construction

Dispenser with Vapor
Barrier Construction

Class 1 Division 1
(Hazardous Location)

Class 1 Division 2
(Hazardous Location)

Vapor Areas

Fuel Containing
Components