beautypg.com

Connecting vapor return line to vapor shear valve – Gasboy Atlas Fuel Systems Installation Manual User Manual

Page 44

background image

Installation

Connecting Vapor Return Line to Vapor Shear Valve

Page 6-14 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014

Connecting Vapor Return Line to Vapor Shear Valve

Do not create any liquid traps when connecting the vapor return line to the vapor line shear
valve (see

Figure 6-6

). A liquid trap is a low place in the vapor return line that can accumulate

fuel and cause blockage, which can cause the system to fail the vapor recovery certification
tests.
Note: The contractor must provide and install the pipe union for connecting to the 1-inch NPT

coupling in the unit. Some regulatory agencies require shear valves or shear sections on
the vapor piping. Follow the guidelines and installation instructions from the vapor
shear valve manufacturer.

Figure 6-6: Correct Vapor Line Connection Method

Correct

Do not allow liquid traps

No place for liquid to
be trapped

Not Allowed

1-inch NPT Vapor Return Pipe
supplied in the Unit

Contractor-supplied
Fittings, Pipe, and Shear
Valve

Contractor-supplied
Fittings, Pipe, and
Shear Valve

Vapor Line Shear Valve