beautypg.com

Installation checklists, Mechanical and hydraulic related items, Installation checklists -24 – Gasboy Atlas Fuel Systems Installation Manual User Manual

Page 54: Mechanical and hydraulic related items -24, Irrespective of whether pur

background image

Installation

Installation Checklists

Page 6-24 MDE-4331M Atlas® Fuel Systems Installation Manual · September 2014

Installation Checklists

To ensure proper and safe operation of all equipment, and to maintain warranty coverage, the
following checklists must be completed at this time. Many of the items on the list must already
have been checked by the electrician as covered earlier. Follow instructions in checklists and
perform all the required inspections. After the inspection is complete, insert forms (less your
copy) in the dispenser’s electronic cabinet and ensure that there is no contact with any of the
electronic component(s). Forms must be provided with each unit; if not, contact the Gasboy
distributor.
Note: Always make copies of checklists for actual use. This way, you will always have an

original to copy and use in the future.

Mechanical and Hydraulic Related Items

Item

Procedure

Refer To

Checked

1

Shear valves must be installed as per the valve manufacturer’s
recommendations. Shear point is ±3/4-inch of grade and properly
mounted.

“Shear Valves”

on

page 7-10

2

Flexible pipes must not be used within the dispenser. However,
flexible pipes meeting local and state codes can be used below the
pump/dispenser, as allowed by regulatory authorities.

MDE-4333 Atlas Fuel
Systems Site
Preparation Manual

3

Pumps (self-contained units) must have a vacuum-actuated pressure
regulating valve to prevent positive pressure at the pump base, when
used with aboveground tanks.

MDE-4333 Atlas Fuel
Systems Site
Preparation Manual

4

Pumps require a check valve.

MDE-4333 Atlas Fuel
Systems Site
Preparation Manual

5

Hose breakaways must be used and installed as per the
manufacturer’s recommendations.

Manufacturer’s
specifications

6

The unit must be properly anchored to the island.

“Model 9850KXTW1
Shear Valve
Configuration”

on

page 6-10

7

Vapor recovery piping at the pump/dispenser must have no traps or
sags.

“Connecting Vapor
Return Line to Vapor
Shear Valve”

on

page 6-14

8

Ensure that the correct nozzles, hoses, and brand panels are
associated with the product being dispensed.

Specific to the unit
order

9

All code, regulatory agency, or customer-specified safety warning
signs, labels, or decals have been installed.

As provided with and
for the unit

10

Long hose lengths beyond Gasboy recommendations must not be
used without special retrievers. For Balance Vapor Recovery, no
portion of the hose may be on the ground.

NFPA 30A

11

Unit mounted using proper quantity, size, and strength mounting
hardware.

“Model 9850KXTW1
Shear Valve
Configuration”

on

page 6-10

12

Wiring color coded or tagged, sized for distance and application, and
resistant to gas and oil.

“Preparing Field
Wiring”

on

page 6-15